Model
|
WK-5235
|
|
Frequency
|
200KHz
|
|
Test Parameter
|
|
Transformer Scanning
|
Turn Ratio, Phase, L, Q, Leakage L, Balance,
|
|
ACR, Cp, D, X, Y, DCR, Pin Short
|
|
Test Signals Information
|
|
Test Frequency (0.01%, 5digits)
|
Turn
|
1kHz~200kHz
|
|
Others
|
20Hz~200kHz
|
|
Output Impedance
|
100Ω
|
|
Measurement Range
|
|
L, LK
|
0.00001uH~9999.99H
|
|
C
|
0.00001pF~999.999mF
|
|
Q, D
|
0.00001~99999
|
|
Z, X, R
|
0.00001Ω~99.9999MΩ
|
|
Y
|
0.01nS~99.9999S
|
|
θ
|
-90.00º~+90.00º
|
|
DCR
|
0.01mΩ~99.999MΩ
|
|
Turn
|
0.01~99999.99turns
|
|
Pin-Short
|
12 pairs, between pin to pin
|
|
Basic Accuracy
|
|
L, LK, C, Z, X, Y, R, DCR
|
0.1% (1kHz if AC parameter)
|
|
Q, D
|
0.0005(1kHz)
|
|
θ
|
0.03º(1kHz)
|
|
Turn
|
0.5%(1kHz)
|
|
Measurement Speed (Fastest)
|
|
L, LK, C, Z, X, Y, R, D, θ
|
75ms
|
|
DCR
|
30m/s
|
|
Turn
|
75ms
|
|
Judge
|
|
Transformer Scanning
|
PASS/FAIL judge of all test parameters
|
|
output from optional HANDLER interface
|
|
Test Channel
|
20 Channels
|
|
Trigger
|
Internal, Manual, External
|
|
Display
|
320*240 dot-matrix LCD display
|
|
Equivalent Circuit Mode
|
Series, Parallel
|
|
Correction Function
|
Open/Short Zeroing, Load deviation
|
|
Memory
|
64 instrument setups
|
|
General
|
40 Pin Test Fixture
|
|
Operation Environment
|
Temperature :10ºC ~ 40ºC, Humidity :10%~90% RH
|
|
Power Consumption
|
140VA max.
|
|
Power Requirement
|
90Vac~125Vac or 190Vac~250Vac, 48Hz~62Hz
|
|
Weight
|
Approx. 9kg
|
|
Dimension (W*H*D)
|
480*180*320mm
|